In the matter of Seeking exemption from having dedicated feeder for availing open access for Solar PV power of CSERC (Connectivity and Intra-State Open Access) Regulations – EQ
Summary:
—
### **1. Case Overview:**
– **Petitioner:** M/s Amrit Metals and Gases LLP (located in Urla Industrial Estate, Raipur)
– **Contract Demand:** 360 KVA
– **Supply:** Connected via 33 kV RIC Feeder from 132 kV Birgaon substation
– **Respondents:**
1. Chhattisgarh State Power Distribution Company Limited (CSPDCL)
2. Chhattisgarh State Power Transmission Company Limited (CSPTCL)
—
### **2. Petitioner’s Request:**
The petitioner sought **exemption from having a dedicated feeder** to avail **intra-state open access** for using solar PV power from its remotely located captive solar plant.
#### **Key Details:**
– **Solar Plant Capacity:** 0.75 MW (AC)
– **Location:** Village Mohbhatta, District Bemetara
– **Connectivity:** Consent granted by CSPDCL (30.09.2025)
– **Injection Point:** 132 kV Saja substation via a pooling substation at Mohbhatta
– **Commissioning Date:** 30.10.2025
#### **Reasons for Exemption:**
– The drawal of solar power for captive use is minimal, making a dedicated feeder unfeasible.
– Clause 5(5) of the **CSERC Open Access Regulations, 2011** empowers the Commission to exempt bulk consumers from dedicated feeder requirements, subject to load restrictions.
—
### **3. Conditions Proposed by Petitioner:**
– Petitioner will develop **data communication facilities** to SLDC.
– Install requisite **metering equipment** (ABT meter, AMR, RTU).
– Agree to **load restrictions** on the common distribution feeder.
– Abide by any other conditions imposed by the Commission.
#### **Additional Request:**
– Units generated between the **synchronization date and ABT meter installation** be treated as **banking units** and adjusted accordingly.
—
### **4. Respondents’ Submissions:**
#### **CSPDCL’s Conditions:**
1. Install **ABT meter with AMR and RTU** at the drawal point.
2. **No claims** in case of feeder failure/maintenance/shutdown of the 33 kV RIC feeder.
3. Submit an undertaking to CSPDCL and CSPTCL accepting the above conditions.
4. **Technical feasibility report** for the 33 kV RIC feeder submitted.
#### **CSPTCL’s Conditions:**
1. Similar to CSPDCL – install ABT meter with AMR/RTU.
2. Accept **no claims** for feeder outages and agree to load restrictions.
3. Submit undertaking to both respondents.
4. Transmission from injection (132 kV Saja) to drawal (132/33 kV Birgaon) is **technically feasible**.
—
### **5. Commission’s Analysis & Decision:**
#### **Key Findings:**
– The Commission has authority under **Regulation 5(5)** to grant exemption from dedicated feeder requirements.
– Petitioner agreed to fulfil all conditions set by respondents.
– The request for **banking units during transition** is allowed **once**, during the **first adjustment period** after exemption is granted, to avoid lapse of banked energy due to procedural delays.
#### **Final Order:**
– **Exemption granted** from dedicated feeder requirement for open access.
– Subject to **fulfilment of respondents’ conditions** (metering, no claims, load restrictions, undertakings).
– Banking of units permitted **only for the first adjustment period** post-exemption.
—